This treatment dosed at 1.49 grams per ton of distilled water provides 1.0 ppm phosphate.
Feed Points: Dose with other BOILER CHEMICAL / alkaline liquid by diluting withcondensate and feed directly into the system drum (below the water level) using a bypass pot feeder. For low-pressure boilers, It may be dosed to the hotwell or condensate return tank, although this is not the preferred method.
Dosage and control
|
|
Phophate test result in pPM PO4
|
|
|
Pressure
|
0 - 10
|
10 - 20
|
20 - 30
|
30 - 40
|
40 - 50
|
> 50
|
Control range
|
|
0-40 Bar
0-588 PSI
|
23
|
11.5
|
Satisfactory
|
Satisfactory
|
Blow Down
|
20-50
|
|
41-60 Bar
589-880 PSI
|
17
|
5.5
|
Satisfactory
|
Blow Down
|
Blow Down
|
15-30
|
|
> 60 Bar
> 880 PSI
|
5.5
|
Satisfactory
|
Satisfactory
|
Blow Down
|
Blow Down
|
10-25
|
Select row on righthand side for applicable pressure range. Compare test result with comment in table and dose stated amount of product per ton boiler water volume.